Basic temperature transmitter offers a reliable solution for
temperature monitoring points.
Standard transmitter design provides flexible and reliable
performance in process environments.
Experience lower over-all installation costs when compared to
wiring sensor directly, reducing the need for
expensive extension wires and multiplexers.
Explore the benefits of a Complete Point Solution from Rosemount
Temperature.
Functional specifications
Inputs
User-selectable; sensor terminals rates to 42.4 Vdc. See
“Transmitter accuracy and ambient temperature effects” on
page 12 for sensor options.
Output
2-wire 4–20 mA, linear with temperature or input; digital output
signal superimposed on 4–20 mA signal, available for a Field
Communicator or control system interface.
Isolation
Input/output isolation tested to 500 Vac rms (707 Vdc) at 50/60
Hz.
Power supply
An external power supply is required for HART devices. The
transmitter operates on 12.0 to 42.4 Vdc transmitter terminal
voltage with load resistance between 250 and 1100 ohms. A
minimum of 17.75 Vdc power supply is required with a load of
250 ohms. Transmitter power terminals are rated to 42.4 Vdc.